Why We Use PIR In Circuit Breaker ?


Pre-Insertion Resistor & Zero Missing Phenomenon




Inside of PIR


Large generation of reactive power occurs in HVAC due to the capacitance of the long transmission lines and cables.

To compensate the reactive power, shunt reactors are typically installed. Due to their inductive characteristics, these can raise other technical challenges within the system.

The current in the inductor should maintain its continuity and when it is connected at a voltage zero, the current will have a DC component with an amplitude equal to the amplitude of the AC component

The duration of the DC component depends on the resistance of system components e.g. resistance of shunt reactor winding, external grid, export cable and transformers.

If the inductor is connected at a peak voltage, no DC component will be present because the current will be zero at that moment.

The capacitive current of the cable and transmission line are leads system voltage by 90 degrees, and inductive current of the shunt reactor lags by 90 degrees.

If energized at voltage zero, both the inductive and capacitive currents are in phase opposition to each other and tend to cancel out. This leaves a DC current in the incoming breaker, with no zero crossing for a period of time.

During this period it is not feasible to re-open the circuit breaker (e.g. if a fault in the cable exists) because the circuit breaker should find the current zero for an arc interruption. This can take a long time (sometimes seconds) to attain. Hence, it is called zero missing phenomenon (ZMP).

There are different mitigation methods addressed in the article for ZMP and the application of any particular the method depends on the system conditions like operating voltage, cable length and location of the system.


Fig. 1 shows the current for the cable or (transmission line) and shunt reactor in phase opposition. These two currents cancel each other out, leaving the DC component.

The magnitude of the DC component depends on the amount of compensation, where lower shunt compensation results in a lower DC component. The ZMP can theoretically be avoided by limiting the compensation to less than 50%.

However, this may increase transient overvoltage, and cause the need for a larger STATCOM / SVC for meeting grid code reactive capability requirements.


EFFECT OF SYSTEM PARAMETERS ON ZERO MISS DURATION:


The duration of ZMP depends on various parameters of the system. It is important to determine the maximum zero miss duration (ZMD) before implementing any mitigation methods.

A. Switching angle


The maximum ZMD is observed when the circuit breaker is switched at voltage zero (simultaneous or single pole). There is no ZMD observed for the circuit breaker when switched at voltage peak (single pole).

B. Grid short circuit strength


The damping of the DC component of the shunt reactor current during energization, and during faults, depends upon positive and zero sequence impedance of the grid. 

The resistance for maximum fault level is less as compared to the minimum fault level, which therefore leads to slower damping of the DC component

C. Degree of compensation


The maximum ZMD is at 100% compensation when the capacitive and inductive currents completely cancel each other out and only the DC component remains. 

Above 100% compensation, the inductive current is greater than capacitive current, and hence, only some AC component remains, resulting in a reduction of the ZMD. There is no ZMD below 50% compensation provided the shunt reactor has a minimum resistance to damp out the DC component.



PRE-INSERTION RESISTOR:


Circuit breakers with pre-insertion resistors (PIR) are often installed to damp out the transients during energization. There are basically two different PIR configurations: parallel and series PIR. 

In parallel PIR configuration (Fig. 3a), the resistor switch is in series with the resistor bank, and both are in parallel with the circuit breaker interrupter, where the interrupter operation follows the PIR switch operation. 

In a series PIR configuration (fig. 3b), the resistor switch is in series with the circuit breaker interrupter but in parallel with the resistor bank.



The different characteristic quantities of a circuit breaker with closing resistors as shown in Fig. 4



The closing time interval is defined as time between energizing the closing circuit, the circuit-breaker being in the open position, and the instant when the contacts touch in all poles.

The make time interval is the time between energizing the closing circuit, the circuit-breaker being in the open position, and the instant when the current begins to flow in the first pole.

Pre-arcing time interval is the time between the initiation of current flow in the first pole during a closing operation, and the instant when the contacts touch in all poles for three-phase conditions, and the instant when the contacts touch in the arcing pole for single-phase conditions.

For a parallel PIR, PIT is defined as the interval of time during a closing operation in any one pole between the instant of contact touch of resistor switch, and the instant of contact touch in the main breaking unit of that pole. 

For circuit breakers having series connected PIR, the PIT is defined as the interval of time between the instant of the last contact touch in any closing resistor element, and the instant of the last contact touch in any main breaking unit.

From the above definition, the PIT for both the configurations are different for different phases. The PIT mentioned in this paper is the time for which the resistor in each pole is in circuit before the contact touching of the main breaking unit of that pole.

The standard also specifies typical manufacturing tolerances for resistors to be considered. If a manufacturer has been selected, they should state the value of these tolerances. 

In addition, they should state the range of PIR insertion times which they can achieve (including time tolerances), as these are typically realized mechanically, and therefore depend on the physical design and ambient conditions.





















Comments